1MRS759142 C
3.25.2.5
3.25.2.6
Table 329:
Diagnostic parameters for X1/LAN, X2/LAN and X3/LAN
Parameter
Values (Range)
Reset counters
FALSE
TRUE
GOOSE limit count
0...1000000
SMV limit count
0...1000000
Ucast limit count
0...1000000
Def. limit count
0...1000000
GOOSE limit alarm
FALSE
TRUE
SMV limit alarm
FALSE
TRUE
Ucast limit alarm
FALSE
TRUE
Def. limit alarm
FALSE
TRUE
REX640
Technical Manual
Monitored data
Monitored data is available in six locations.
•
Monitoring/Communication/Ethernet/Activity/CH1LIV
•
Monitoring/Communication/Ethernet/Activity/CH2LIV
•
Monitoring/Communication/Ethernet/Activity/CH3LIV
•
Monitoring/Communication/Ethernet/Link statuses/LNK1LIV
•
Monitoring/Communication/Ethernet/Link statuses/LNK2LIV
•
Monitoring/Communication/Ethernet/Link statuses/LNK3LIV
Diagnostics
Diagnostics data is available in Monitoring/Communication/Ethernet/
Diagnostics/Xn (n = 1...3).
Unit
Step
Default
FALSE
0
0
0
0
FALSE
FALSE
FALSE
FALSE
Section 3
Basic functions
Description
Reset counters
command
Goose rate limit
exceed count
Sampled measured
values limit exceed
count
Unicast rate limit
exceed count
Default rate limit
exceed count
Goose rate limit
exceed alarm
Sampled measured
values limit alarm
Unicast rate limit
exceed alarm
Default rate limit
exceed alarm
299