1MRS759142 C
3.17.3
3.17.3.1
3.17.3.2
3.17.3.3
REX640
Technical Manual
Phase and residual voltage preprocessing UTVTR
Identification
Function description
Phase and residual voltage
preprocessing
Function block
GUID-615F9CAA-66C6-4906-A438-2E0CA3C31228 V2 EN
Figure 72:
Function block
Functionality
The phase and residual voltage preprocessing function UTVTR is used for setting up
the three phase voltage measurement channels and residual voltage measurement. The
input channels for UTVTR are either physical hardware or IEC 61850-9-2 sampled
value channels.
The output channel U3P of UTVTR can be connected to different applications which
require phase voltage, positive and negative sequence.
Outputs URES_MEAS and URES_CLC can be connected to different applications
which require measured residual voltage or calculated residual voltage (from phase
voltages), respectively.
If only two phase-to-earth voltages are available, then the third phase-
to-earth voltage can be calculated without URES input connected
(assumed to be zero in that case). Positive- and negative-sequence
components are also calculated using these voltages. The accuracy of
the calculated values is affected if the actual residual voltage is not
zero.
IEC 61850
IEC 60617
identification
identification
UTVTR
UTVTR
Section 3
Basic functions
ANSI/IEEE C37.2
device number
UTVTR
187