PCM600 parameters
EIHMI contains three paths to populate parameters visible in Parameter Setting in
PCM600.
Configuration/HMI
Monitoring/Detached LHMI
Information/HW modules/EIHMI1

Application

Substation HMI wake-up (door sensor)
In this example, substation HMI devices need to be woken up when a person enters the
substation to see that everything works as expected.
A switch signal is directly connected to the binary input, which activates the paired
HMI.
Depending on the hardware solution, this hardware signal can be distributed to all
affected protection relays on the substation. Optionally, the processed signal can be
routed in horizontal communication through process bus communications, that is,
GOOSE, to other protection relays.
GUID-0C0DD4BF-399F-4E1F-A7A4-EA8F212785C8 V1 EN
Figure 171:
Binary input connection

Signals

Table 330:
EIHMI Input signals
Name
Type
WAKEUP
BOOLEAN
Default
Description
0=False
HMI wakeup command
Section 3
Basic functions
301