Section 4
Protection functions
566
GUID-903978C2-D0AC-4737-89DA-0BEA9CB30B9B V1 EN
Figure 312:
Connection example of current transformers of Type 2
Transformer vector group matching
Before differential and bias currents can be calculated, the phase difference of the
currents must be vector group matched based on the transformer connection type. The
vector group of the power transformer is numerically matched on the high voltage and
low voltage sides by means of the Winding selection, Winding 1 type, Winding 2 type
and Clock number settings. Thus no interposing CTs are needed if there is only a
power transformer inside the protected zone. The matching is based on phase shifting
and a numerical delta connection in the protection relay. If the neutral of a star-
connected power transformer is earthed, any earth-fault in the network is perceived by
the protection relay as a differential current. The elimination of the zero-sequence
1MRS759142 C
REX640
Technical Manual