Received GOOSE interlocking information
GOOSERCV_INTL

Function block

GUID-EFA94662-CF1C-4A1E-ABA8-52238A6FD227 V1 EN
Figure 80:
Function block

Functionality

The received GOOSE interlocking information function GOOSERCV_INTL is used
to connect the GOOSE double binary input to the application and extracting single
binary position signals from the double binary position signal.
The OP output signal indicates that the position is open. Default value (0) is used if
VALID output indicates invalid status.
The CL output signal indicates that the position is closed. Default value (0) is used if
VALID output indicates invalid status.
The OK output signal indicates that the position is neither in faulty or intermediate
state. The default value (0) is used if VALID output indicates invalid status.

Signals

Table 144:
GOOSERCV_INTL Input signals
Name
Type
IN
Dbpos
Table 145:
GOOSERCV_INTL Output signals
Name
Type
OP
BOOLEAN
CL
BOOLEAN
OK
BOOLEAN
VALID
BOOLEAN
Basic functions
Default
Description
00
Input signal
Description
Position open output signal
Position closed output signal
Position OK output signal
Output signal