Section 4
Protection functions
Parameter
R0 zone 1
X0 zone 1
Factor K0 zone 1
Factor K0 angle Zn1
Min Ris Gnd Rch Zn1
Max Ris Gnd Rch Zn1
Gnd operate Dl Zn1
Directional mode Zn2
Op Mod PP loops Zn2
PP Op delay Mod Zn2
R1 zone 2
X1 zone 2
X1 reverse zone 2
Z1 zone 2
Z1 angle zone 2
Z1 reverse zone 2
Min Ris PP Rch Zn2
Max Ris PP Rch Zn2
PP Op delay Mod Zn2
Op Mod Gnd loops Zn2
Gnd Op Dl mode Zn2
Load Comp zone 2
R0 zone 2
X0 zone 2
Factor K0 zone 2
Factor K0 angle Zn2
Min Ris Gnd Rch Zn2
Table continues on next page
910
Values (Range)
Unit
0.00...3000.00
ohm
0.00...3000.00
ohm
0.0...4.0
-135...135
deg
0.00...500.00
ohm
0.00...500.00
ohm
20...60000
ms
1=Non-directional
2=Forward
3=Reverse
0=False
1=True
0=False
1=True
0.00...3000.00
ohm
0.00...3000.00
ohm
0.00...3000.00
ohm
0.01...3000.00
ohm
15.0...90.0
deg
0.00...3000.00
ohm
0.00...100.00
ohm
0.00...100.00
ohm
20...60000
ms
0=False
1=True
0=False
1=True
0=False
1=True
0.00...3000.00
ohm
0.00...3000.00
ohm
0.0...4.0
-135...135
deg
0.00...500.00
ohm
Step
Default
0.01
160.00
0.01
160.00
0.1
1.0
1
0
0.01
100.00
0.01
100.00
1
20
2=Forward
0=False
1=True
0.01
40.00
0.01
40.00
0.01
40.00
0.01
56.57
0.1
45.0
0.01
56.57
0.01
30.00
0.01
30.00
1
20
0=False
1=True
1=True
0.01
160.00
0.01
160.00
0.1
1.0
1
0
0.01
100.00
1MRS759142 C
Description
Zero sequence resistive reach, zone 1
Zero sequence reactive reach, zone 1
Residual compensation factor magnitude,
zone 1
Residual compensation factor angle,
zone 1
Minimum resistive reach of PE-loops,
zone 1
Maximum resistive reach of PE-loops,
zone 1
Time delay to operate of PE-loops, zone 1
Directional mode, zone 2
Enable PP/3P-loop measurement, zone 2
Enable operate timer for PP/3P-loops,
zone 2
Positive sequence resistive reach, zone 2
Positive sequence reactive reach, zone 2
Pos. seq. reactive reach in rev. dir., non-
dir. zone 2
Positive sequence reach, zone 2
Positive sequence line angle, zone 2
Positive sequence reach in rev. dir., non-
dir. zone 2
Minimum resistive reach of PP/3P-loops,
zone 2
Maximum resistive reach of PP/3P-loops,
zone 2
Enable operate timer for PP/3P-loops,
zone 2
Enable PE-loop measurement, zone 2
Enable operate timer for PE-loops, zone 2
Enable load compensation for PE-loops,
zone 2
Zero sequence resistive reach, zone 2
Zero sequence reactive reach, zone 2
Residual compensation factor magnitude,
zone 2
Residual compensation factor angle,
zone 2
Minimum resistive reach of PE-loops,
zone 2
Technical Manual
REX640