Signals; Settings; Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.4.4.7
4.4.4.8
Table 691:
PREVPTOC Group settings (Basic)
Parameter
Start value
Operate delay time
Table 692:
PREVPTOC Non group settings (Basic)
Parameter
Operation
4.4.4.9
756

Signals

Table 689:
PREVPTOC Input signals
Name
I3P
BLOCK
Table 690:
PREVPTOC Output signals
Name
OPERATE
START

Settings

Values (Range)
Unit
0.05...1.00
xIn
100...60000
ms
Values (Range)
Unit
1=on
5=off

Monitored data

Table 693:
PREVPTOC Monitored data
Name
START_DUR
PREVPTOC
Type
Default
Description
SIGNAL
-
Three-phase currents
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.01
0.75
10
100
Step
Default
1=on
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS759142 C
Description
Start value
Operate delay time
Description
Operation Off / On
Unit
Description
%
Ratio of start time /
operate time
Status
Technical Manual
REX640

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents