Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
Table 853:
DSTPDIS Non group settings (Advanced)
Parameter
EF Cur stabilization
Fact EF current Bal
Zone timer mode
Voltage Mem time
4.7.1.10
916
Values (Range)
Unit
0=False
1=True
1.000...2.000
1=Independent
2=Common
0...300000
ms

Monitored data

Table 854:
DSTPDIS Monitored data
Name
STARTS_GFC
RELEASE_PE
RELEASE_PP
EARTH_FLT
DIR_E_FLT
STARTS_Z1
STARTS_Z2
STARTS_Z3
STARTS_Z4
STARTS_Z5
Table continues on next page
Step
Default
0=False
0.001
1.200
1=Independent
10
40
Type
Values (Range)
Enum
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
-5=No fault
1=AG Fault
2=BG Fault
3=CG Fault
Enum
-5=No fault
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
Enum
5=BC Fault
6=CA Fault
7=ABC Fault
4=AB Fault
-5=No fault
BOOLEAN
0=False
1=True
Enum
0=unknown
1=forward
2=backward
3=both
INT32
-5...31
INT32
-5...31
INT32
-5...31
INT32
-5...31
INT32
-5...31
1MRS759142 C
Description
EF current stabilization enabled
Residual current ratio for parallel line
compensation
Operate timer start mode, zones
Voltage memory time
Unit
Description
Start signals for phases
A, B and C, GFC
Release signals for PE-
loops, GFC
Release signals for
PP/3P loops, GFC
Indication of a single
phase earth-fault, GFC
Earth-fault direction (low
imp. earthed), GFC
Start signals for phases
A, B and C, zone 1
Start signals for phases
A, B and C, zone 2
Start signals for phases
A, B and C, zone 3
Start signals for phases
A, B and C, zone 4
Start signals for phases
A, B and C, zone 5
Technical Manual
REX640

Hide quick links:

Advertisement

Table of Contents
loading