Section 8
Measurement functions
8.2.6
8.2.7
Table 1283:
RDRE Non group general settings (basic)
Parameter
Values (Range)
Operation
1=on
5=off
Record length
10...500
Pre-trg length
0...100
Table 1284:
RDRE Non group general settings (advanced)
Parameter
Values (Range)
Operation mode
1=Overwrite
2=Saturation
Exclusion time
0...1 000 000
Storage rate
32, 16, 8
Periodic trig time
0...604 800
Stor. mode periodic
0=Waveform
1=Trend / cycle
Table continues on next page
1340
The binary channels are sampled once per task execution of the disturbance recorder.
The task execution interval for the disturbance recorder is the same as for the
protection functions. During the COMTRADE conversion, the digital status values
are repeated so that the sampling frequencies of the analog and binary channels
correspond to each other. This is required by the COMTRADE standard.
The disturbance recorder follows the 1999 version of the
COMTRADE standard and uses the binary data file format.

Signals

Table 1282:
RDRE Output signals
Name
TRIGGERED
Settings
Unit
cycles
%
Unit
ms
samples per
fundamental cycle
s
Type
BOOLEAN
Step
Default
1=on
1
50
1
50
Step
Default
2
10
0
32
10
0
0
1MRS759142 C
Description
Recording started
Description
Disturbance
recorder on / off
Record length in
fundamental cycles
Length of the
recording preceding
the triggering
Description
Saturation /
overwrite
The time during
which triggerings of
same type are
ignored
Storage rate for
waveform
recordings in
samples per cycle
Time between
periodic triggerings
in seconds
Storage mode
selection
(waveform / trend)
for periodic trigger
REX640
Technical Manual