1MRS759142 C
5.1.8
Table 1001:
INRPHAR Group settings (Basic)
Parameter
Values (Range)
Start value
Operate delay time
Table 1002:
INRPHAR Group settings (Advanced)
Parameter
Values (Range)
Min operate current
Table 1003:
INRPHAR Non group settings (Basic)
Parameter
Values (Range)
Operation
Table 1004:
INRPHAR Non group settings (Advanced)
Parameter
Values (Range)
Num of start phases
Reset delay time
5.1.9
REX640
Technical Manual

Settings

Unit
5...100
%
20...60000
ms
Unit
5...500
%In
Unit
1=on
5=off
Unit
1=1 out of 3
2=2 out of 3
0...60000
ms
Monitored data
Table 1005:
INRPHAR Monitored data
Name
INRPHAR
Step
Default
1
20
1
20
Step
Default
1
5
Step
Default
1=on
Step
Default
1=1 out of 3
1
20
Type
Values (Range)
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection related functions
Description
Ratio of the 2. to the 1. harmonic leading
to restraint
Operate delay time
Description
Minimum fundamental component of
phase current for activation
Description
Operation Off / On
Description
Number of phases required for operate
activation
Reset delay time
Unit
Description
Status
Section 5
1065