Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.

Operation principle

The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of SEQSPVC can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
U
U_A_AB
U3P
U_B_BC
U_C_CA
CB_CLOSED
I_A
I_B
I_C
I3P
I
DISCON_OPEN
MINCB_OPEN
BLOCK
GUID-876A3950-E9C6-4879-9FA6-303148912F04 V1 EN
Figure 669:
Functional module diagram
Negative phase-sequence criterion
A fuse failure based on the negative-sequence criterion is detected if the measured
negative-sequence voltage exceeds the set Neg Seq voltage Lev value and the
measured negative-sequence current is below the set Neg Seq current Lev value. The
detected fuse failure is reported to the decision logic module.
Voltage check
The phase voltage magnitude is checked when deciding whether the fuse failure is a
three, two or a single-phase fault.
Negative
phase
sequence
criterion
2
Voltage
check
Dead line
detection
&
Current and
voltage
delta
criterion
2
1MRS759142 C
FUSEF_3PH
Decision
FUSEF_U
logic
FUSEF_Z
Technical Manual