Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 6
Supervision functions
6.6.6
6.6.7
Table 1167:
MDSOPT Non group settings (Basic)
Parameter
Operation
Warning value
Alarm value
Table 1168:
MDSOPT Non group settings (Advanced)
Parameter
Initial value
Operating time hour
Operating time mode
1236

Signals

Table 1165:
MDSOPT Input signals
Name
BLOCK
POS_ACTIVE
RESET
Table 1166:
MDSOPT Output signals
Name
ALARM
WARNING
Settings
Values (Range)
Unit
1=on
5=off
0...299999
h
0...299999
h
Values (Range)
Unit
0...299999
h
0...23
h
1=Immediate
2=Timed Warn
3=Timed Warn Alm
Type
Default
Description
BOOLEAN
0=False
Block input status
BOOLEAN
0=False
When active indicates the equipment is running
BOOLEAN
0=False
Resets the accumulated operation time to initial
value
Type
Description
BOOLEAN
Alarm accumulated operation time exceeds Alarm
value
BOOLEAN
Warning accumulated operation time exceeds
Warning value
Step
Default
1=on
1
8000
1
10000
Step
Default
1
0
1
0
1=Immediate
1MRS759142 C
Description
Operation Off / On
Warning value for operation time
supervision
Alarm value for operation time supervision
Description
Initial value for operation time supervision
Time of day when alarm and warning will
occur
Operating time mode for warning and
alarm
Technical Manual
REX640

Hide quick links:

Advertisement

Table of Contents
loading