Signals; Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.5.10.7
4.5.10.8
Table 798:
PHVPTOV Group settings (Basic)
Parameter
Start value
Time interval
Operate delay Mult
Table 799:
PHVPTOV Non group settings (Basic)
Parameter
Operation
Num of start phases
Voltage selection
Table 800:
PHVPTOV Non group settings (Advanced)
Parameter
Relative hysteresis
836

Signals

Table 796:
PHVPTOV Input signals
Name
U3P
BLOCK
INITIALIZE
RESET
Table 797:
PHVPTOV Output signals
Name
OPERATE
START

Settings

Values (Range)
Unit
0.05...3.00
xUn
1...120
min
0...100
Values (Range)
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
1=phase-to-earth
2=phase-to-phase
Values (Range)
Unit
1.0...5.0
%
Type
Default
Description
SIGNAL
-
Three-phase voltages
BOOLEAN
0=False
Block signal for activating the blocking mode
BOOLEAN
0=False
Initialize the voltage average measurement
BOOLEAN
0=False
Reset the voltage average measurement values
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.01
1.10
1
10
1
1
Step
Default
1=on
1=1 out of 3
1=phase-to-earth
Step
Default
0.1
4.0
1MRS759142 C
Description
Start value
Time interval for average voltage
calculation
Trip delay expressed as a multiple of
refresh time
Description
Operation Off / On
Number of phases required for operate
activation
Parameter to select phase or phase-to-
phase voltages
Description
Relative hysteresis for operation
Technical Manual
REX640