ABB RELION REX640 Technical Manual page 895

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
REX640
Technical Manual
R
1
~
GUID-BE30020E-397F-44FC-84B9-77D307E0DB55 V1 EN
Figure 481:
The fault loop impedance model for phase-to-phase impedance
measuring elements
R
Positive-sequence resistance from measuring point to fault location
1
X
Positive-sequence reactance from measuring point to fault location
1
R
Physical fault resistance between phases, for example, arc resistance
F
The phase-to-phase impedance measuring elements measure only
half of the physical fault resistance between phases. This must be
taken into account when the resistive reach of the phase-to-phase
elements is set (that is, setting the value of 5 Ω corresponds to 5 + 5=10
Ω of physical arc resistance between phases).
The resistive reach setting is common for phase-to-phase and three-phase impedance
measuring elements.
The operation time delay is defined with the setting PP operate delay Znx (x = 1... 5).
The timer can be disabled with the setting PP Op delay Mod Znx = "False". This blocks
the OPERATE_Zx (x = 1... 5) output of the phase-to-phase measuring elements.
Three-phase impedance measuring element
DSTPDIS has a dedicated measuring element for a three-phase short circuit fault for
each zone. The three-phase measuring element uses the positive-sequence quantities
for a fault loop impedance estimation which increases the accuracy by reducing the
influence of line parameter asymmetry. This is advantageous especially in case of
non-transposed, asymmetrical lines. The three-phase impedance measuring element
is enabled together with the phase-to-phase impedance elements by the setting Op
Mod PP loops Znx (x = 1... 5) = "True".
The reach of the three-phase measuring element is based on the loop impedance
X
1
R
/2
F
Section 4
Protection functions
X
X
1
R
/2
F
R
1
R
889

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents