Section 4
Protection functions
4.7.3.8
Table 872:
UEXPDIS Group settings (Basic)
Parameter
Diameter
Offset
Displacement
Operate delay time
Table 873:
UEXPDIS Non group settings (Basic)
Parameter
Operation
External Los Det Ena
Voltage reversal
Impedance Meas mode
Phase Sel for Z Clc
Table 874:
UEXPDIS Non group settings (Advanced)
Parameter
Reset delay time
4.7.3.9
940

Settings

Values (Range)
Unit
1...6000
%Zn
-1000...1000
%Zn
-1000...1000
%Zn
60...200000
ms
Values (Range)
Unit
1=on
5=off
0=Disable
1=Enable
0=No
1=Yes
1=1Phase-to-earth
2=1Phase-to-
phase
3=3Phase-to-earth
4=3Phase-to-
phase
5=Pos sequence
1=A or AB
2=B or BC
3=C or CA
Values (Range)
Unit
0...60000
ms
Monitored data
Table 875:
UEXPDIS Monitored data
Name
START_DUR
Z_AMPL_A
Z_ANGLE_A
Z_AMPL_B
Table continues on next page
Step
Default
1
200
1
-10
1
0
10
5000
Step
Default
1=on
1=Enable
0=No
5=Pos sequence
1=A or AB
Step
Default
10
3000
Type
Values (Range)
FLOAT32
0.00...100.00
FLOAT32
0.00...200.00
FLOAT32
-180.00...180.00
FLOAT32
0.00...200.00
1MRS759142 C
Description
Diameter of the Mho diagram
Offset of top of the impedance circle from
the R-axis
Displacement of impedance circle centre
from the X-axis
Operate delay time
Description
Operation Off / On
Enable external excitation loss detection
Rotate voltage signals by 180 degrees
Select voltage and currents for
impedance calculation
Voltage phase selection
Description
Reset delay time
Unit
Description
%
Ratio of start time /
operate time (in %)
xZn
Impedance amplitude
phase A
deg
Impedance angle phase
A
xZn
Impedance amplitude
phase B
Technical Manual
REX640