Settings - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
9.2.7
Table 1322:
P3SXSWI Non group settings (Basic)
Parameter
Values (Range)
Operation
Control mode
Reed contact
Select timeout
Control model
Operation timeout DC
Operation timeout ES
Motor braking
Identification
Table 1323:
P3SXSWI Non group settings (Advanced)
Parameter
Values (Range)
Operation counter DC
Operation counter ES
Event delay
Motor start timeout
Motor brake time
Table continues on next page
REX640
Technical Manual
Name
EXE_ESOPEN
EXE_ESCLOSE
H_UP_LEFT
H_UP_RIGHT
H_LO_LEFT
H_LO_RIGHT

Settings

Unit
1=on
5=off
1=Direct control
2=With RIO600
SCM
0=Not available
1=Available
10000...300000
ms
0=status-only
1=direct-with-
normal-security
4=sbo-with-
enhanced-security
10...60000
ms
10...60000
ms
0=False
1=True
Unit
0...10000
0...10000
0...60000
ms
0...32000
ms
10...500
ms
Type
Description
BOOLEAN
Command to RIO600 SCM for opening earthing
switch
BOOLEAN
Command to RIO600 SCM for closing earthing
switch
BOOLEAN
H-bridge output upper left
BOOLEAN
H-bridge output upper right
BOOLEAN
H-bridge output lower left
BOOLEAN
H-bridge output lower right
Step
Default
1=on
1=Direct control
0=Not available
10000
30000
4=sbo-with-
enhanced-security
1
30000
1
30000
1=True
P3SXSWI1 switch
position
Step
Default
1
0
1
0
1
10000
100
0
1
100
Section 9
Control functions
Description
Operation Off / On
Direct control or RIO600 SCM control
Availability of reed contact
Select timeout in ms
Select control model
Timeout for negative termination for
disconnector
Timeout for negative termination for
earthing switch
Motor braking on/off selection
Control object identification
Description
Disconnector operation cycles
Earthing switch operation cycles
Event delay of intermediate or faulty
position
Timeout for motor to start
Motor brake time