1MRS759142 C
9.4.5
9.4.6
REX640
Technical Manual
eliminated by filtering. The binary input filtering time can be adjusted separately for
each digital input used by the function block. The validity of digital inputs that
indicate the object state is used as additional information in indications and event
logging.
Table 1331:
Status indication
Input
POSOPEN
POSCLOSE
1=True
0=False
0=False
1=True
1=True
1=True
0=False
0=False

Application

In the field of distribution and sub-transmission automation, the reliable control and
status indication of primary switching components both locally and remotely is in a
significant role. These features are needed especially in modern remote controlled
substations. The application area of DCSXSWI and ESSXSWI functions covers
remote and local status indication of, for example, disconnectors, air-break switches
and earthing switches, which represent the lowest level of power switching devices
without short-circuit breaking capability.
Signals
Table 1332:
DCSXSWI Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
Table 1333:
ESSXSWI Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
Table 1334:
DCSXSWI Output signals
Name
Type
OPENPOS
BOOLEAN
CLOSEPOS
BOOLEAN
OKPOS
BOOLEAN
Status
Output
POSITION
OKPOS
(Monitored
data)
1=Open
1=True
2=Closed
1=True
3=Faulty/Bad
0=False
(11)
0=Intermediat
0=False
e (00)
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
Description
Apparatus open position
Apparatus closed position
Apparatus position is ok
Section 9
Control functions
OPENPOS
CLOSEPOS
1=True
0=False
0=False
1=True
0=False
0=False
0=False
0=False
1383