Section 4
Protection functions
4.8.2.7
4.8.2.8
Table 902:
DOPPDPR Group settings (Basic)
Parameter
Start value
Operate delay time
Directional mode
Power angle
Table 903:
DOPPDPR Non group settings (Basic)
Parameter
Operation
Measurement mode
Table 904:
DOPPDPR Non group settings (Advanced)
Parameter
Reset delay time
Pol reversal
968

Signals

Table 900:
DOPPDPR Input signals
Name
I3P
U3P
BLOCK
Table 901:
DOPPDPR Output signals
Name
OPERATE
START
Settings
Values (Range)
Unit
0.01...2.00
xSn
40...300000
ms
2=Forward
3=Reverse
-90...90
deg
Values (Range)
Unit
1=on
5=off
1=PhsA, PhsB,
PhsC
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
Values (Range)
Unit
0...60000
ms
0=False
1=True
Type
Default
Description
SIGNAL
-
Three-phase currents
SIGNAL
-
Three-phase voltages
BOOLEAN
0=False
Block signal for activating the blocking mode
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.01
1.00
10
40
2=Forward
1
0
Step
Default
1=on
3=Pos Seq
Step
Default
10
20
0=False
1MRS759142 C
Description
Start value
Operate delay time
Directional mode
Adjustable angle for power
Description
Operation On/Off
Selection of power calculation method
Description
Reset delay time
Reverse the definition of the power
direction
Technical Manual
REX640