Section 4
Protection functions
4.3.6.7
696
in any busbar section, the difference current is no longer zero and the protection
operates.
GUID-9EB74EDD-C063-477D-BDAF-006AF2795BEC V1 EN
Figure 387:
Differential protection on busbar with bus coupler (Single-phase
representation)
Example calculations for busbar high-impedance differential protection
The protected object in the example for busbar differential protection is a single-bus
system with two zones of protection.
1MRS759142 C
REX640
Technical Manual