1MRS759142 C
REX640
Technical Manual
GUID-54795C25-DC3D-49DB-8CA3-D1C2426E209E V1 EN
Figure 186:
Configurable operating sectors
Table 368:
Momentary per phase direction value for monitored data view
Criterion for per phase direction information
The ANGLE_X is not in any of the defined sectors,
or the direction cannot be defined due too low
amplitude
The ANGLE_X is in the forward sector
The ANGLE_X is in the reverse sector
(The ANGLE_X is in both forward and reverse
sectors, that is, when the sectors are overlapping)
Table 369:
Momentary phase combined direction value for monitored data view
Criterion for phase combined direction information The value for DIRECTION
The direction information (DIR_X) for all phases is
unknown
The direction information (DIR_X) for at least one
phase is forward, none being in reverse
The direction information (DIR_X) for at least one
phase is reverse, none being in forward
The direction information (DIR_X) for some phase
is forward and for some phase is reverse
Protection functions
The value for DIR_A/_B/_C
0 = unknown
1 = forward
2 = backward
3 = both
0 = unknown
1 = forward
2 = backward
3 = both
Section 4
333