Section 3
Basic functions
Parameter
Input threshold
hysteresis
Input osc. level
Input osc. hyst
Table 10:
Network address settings
Parameter
IP address
Subnet mask
Default gateway
Mac address
Table 11:
System settings
Parameter
Rated frequency
Phase rotation
Blocking mode
Bay name
IDMT Sat point
Frequency adaptivity
SMV Max Delay
1) Delay given for 50 Hz/60 Hz
Table 12:
HMI settings
Parameter
FB naming convention
Default view
Backlight timeout
Table continues on next page
72
Values (Range)
Unit
10...50
%
2...50
events/s
2...50
events/s
Values (Range)
Unit
Values (Range)
Unit
1=50Hz
2=60Hz
1=ABC
2=ACB
1=Freeze timer
2=Block all
3=Block OPERATE
output
10...50
I/I>
0=Disable
1=Enable
0=2/2 ms
1=3/3 ms
2=5/4 ms
3=6/5 ms
4=7/6 ms
Values (Range)
Unit
1=IEC61850
2=IEC60617
3=ANSI
1=Measurements
2=Main menu
3=SLD
1...60
min
Step
Default
2
10
1
30
1
10
Step
Default
192.168.2.10
255.255.255.0
192.168.2.1
XX-XX-XX-XX-
XX-XX
Step
Default
1=50Hz
1=ABC
1=Freeze timer
REX640
1
50
0=Disable
1=3/3 ms
Step
Default
1=IEC61850
1=Measurements
1
3
1MRS759142 C
Description
Global binary input hysteresis for all slots
Binary input oscillation suppression
threshold
Binary input oscillation suppression
hysteresis
Description
IP address for Network1
Subnet mask for Network1
Default gateway for Network1
Mac address for Network1
Description
Rated frequency of the network
Phase rotation order
Behaviour for function BLOCK inputs
Bay name in system
Overcurrent IDMT saturation point
Enabling frequency adaptivity
SMV Maximum allowed delay
Description
FB naming convention used in the
protection relay
LHMI default view
LHMI backlight timeout
Technical Manual