Section 3
Basic functions
3.16.1
3.16.1.1
3.16.1.2
3.16.1.3
Table 117:
SMVSENDER Settings
Parameter
Values (Range)
Operation
1=on
5=off
3.16.2
3.16.2.1
180
SMV stream sender (IEC 61850-9-2LE) SMVSENDER
Function block
GUID-BE43AAAD-DF4C-49D9-AE8D-4A49CDF8FB3B V1 EN
Figure 68:
Function block
Functionality
The SMV stream sender (IEC 61850-9-2LE) function SMVSENDER is used for
activating the SMV sending functionality. It adds/removes the sampled value control
block and the related data set into/from the sending device's configuration. It has only
input signals.
SMVSENDER can be disabled with the Operation setting value "off". Toggling
SMVSENDER "on" or "off" can be done from the LHMI. When disabled, the sending
of the sample values is disabled.
Settings
Unit
SMV stream receiver (IEC 61850-9-2LE) SMVRCV
Function block
GUID-12A2F14F-1BC1-4BAA-A9B9-2C5A32C37099 V1 EN
Figure 69:
Function block
Step
Default
1=on
1MRS759142 C
Description
Operation
REX640
Technical Manual