Real Greater Than Or Equal Comparator Ger; Function Block; Functionality - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 3
Basic functions
3.22.7
3.22.7.1
3.22.7.2
284

Real greater than or equal comparator GER

Function block

GUID-990E585B-093C-4811-B1AE-2492A6B3816E V1 EN
Figure 157:
Function block

Functionality

The real greater than or equal comparator function GER compares the real input
REAL_IN1 with the real input REAL_IN2 and activates the binary output OUT if
REAL_IN1 is equal to or greater than REAL_IN2 - TOLR or greater than input
REAL_IN2. That is, if REAL_IN1≥ (REAL_IN2 - TOLR) or REAL_IN1 >
(REAL_IN2), OUT = 1, else OUT = 0.
If input REAL_IN1 or REAL_IN2 is outside the range, then OUT is set to 0.
Max 2097151.000
REAL_IN2
REAL_IN2-TOLR
GUID-9CED68CA-CD0C-426C-9527-E4EAB5F9FB4B V1 EN
Figure 158:
Region of GER comparison
GER function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
closely varying values.
Greater than region
Equal region
1MRS759142 C
REX640
Technical Manual