Goose Function Blocks; Received Goose Binary Information Goosercv_Bin; Function Block - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Table 132:
UTVTR (Uo) Non group settings (Basic)
Parameter
Values (Range)
Primary voltage
Secondary voltage
Amplitude Corr
Angle correction
Table 133:
UTVTR (Uo) Non group settings (Advanced)
Parameter
Values (Range)
Frequency adaptivity
3.18
3.18.1
3.18.1.1
REX640
Technical Manual
Unit
0.100...440.000
kV
57...240
V
0.9000...1.1000
-20.0000...20.0000
deg
Unit
0=Disable
1=Enable

GOOSE function blocks

GOOSE function blocks are used for connecting incoming GOOSE data to
application. They support BOOLEAN, Dbpos, Enum, FLOAT32, INT8 and INT32
data types.
Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by bad
data quality bits or GOOSE communication failure. See IEC 61850 engineering guide
for details.
The OUT output passes the received GOOSE value for the application. Default value
(0) is used if VALID output indicates invalid status. The IN input is defined in the
GOOSE configuration and can always be seen in SMT sheet.
Settings
The GOOSE function blocks do not have any parameters available in LHMI or
PCM600.

Received GOOSE binary information GOOSERCV_BIN

Function block

GUID-180C83BD-FD74-40F7-8339-08839B2D805D V1 EN
Figure 75:
Function block
Step
Default
0.001
11.547
1
100
0.0001
1.0000
0.0001
0.0000
Step
Default
0=Disable
Section 3
Basic functions
Description
Primary voltage
Secondary voltage
Amplitude correction
Angle correction factor
Description
Frequency adaptivity selection
193

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents