Section 3
Basic functions
Table 187:
TPSGAPC Non group settings (Basic)
Parameter
Pulse time
214
Function block
GUID-CF4909ED-D729-4231-BFBA-0733FAA6098B V1 EN
Figure 99:
Function block
Functionality
The minimum pulse timer second resolution, two channels, function TPSGAPC
contains two independent timers. The function has a settable pulse length (in seconds).
The timers are used for setting the minimum pulse length for example, the signal
outputs. Once the input is activated, the output is set for a specific duration using the
Pulse time setting. Both timers use the same setting parameter.
GUID-B744FA36-0C8F-42B5-8237-503FE49C80C2 V1 EN
Figure 100:
A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is
longer than Pulse time setting
Signals
Table 185:
TPSGAPC Input signals
Name
IN1
IN2
Table 186:
TPSGAPC Output signals
Name
OUT1
OUT2
Settings
Values (Range)
Unit
0...300
s
Type
Default
Description
BOOLEAN
0=False
Input 1
BOOLEAN
0=False
Input 2
Type
Description
BOOLEAN
Output 1 status
BOOLEAN
Output 2 status
Step
Default
1
0
1MRS759142 C
Description
Minimum pulse time
Technical Manual
REX640