Ethernet Channel Supervision Schlcch; Function Block; Functionality; Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Parameter
Values (Range)
Def. limit count
0...1000000
GOOSE limit alarm
FALSE
TRUE
SMV limit alarm
FALSE
TRUE
Ucast limit alarm
FALSE
TRUE
Def. limit alarm
FALSE
TRUE
3.25.2
3.25.2.1
3.25.2.2
3.25.2.3
REX640
Technical Manual
Unit

Ethernet channel supervision SCHLCCH

Function block

GUID-63326B82-5240-4CDD-BE3F-92D5E077067B V1 EN
Figure 169:
Function block

Functionality

Ethernet channel supervision SCHLCCH represents X1/LAN, X2/LAN and X3/LAN
Ethernet channels.
An unused Ethernet port can be set "Off" with the setting Configuration/
Communication/Ethernet/Port Modes. This setting closes the port from software,
disabling the Ethernet communication in that port. Closing an unused Ethernet port
enhances the cyber security of the relay.

Signals

Table 325:
SCHLCCH1 Output signals
Name
Type
CH1LIV
BOOLEAN
LNK1LIV
BOOLEAN
Step
Default
0
FALSE
FALSE
FALSE
FALSE
Description
Status of Ethernet channel X1/LAN
When
Redundant mode is set to "None" or port is not
one of the redundant ports (LAN A or LAN B), value is
TRUE if the port is receiving Ethernet frames.
Otherwise the value is FALSE.
Link status of Ethernet port X1/LAN
Value is "Up" or "Down".
Section 3
Basic functions
Description
Default rate limit
exceed count
Goose rate limit
exceed alarm
Sampled measured
values limit alarm
Unicast rate limit
exceed alarm
Default rate limit
exceed alarm
297