ABB RELION REX640 Technical Manual page 182

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 3
Basic functions
Parameter
Values (Range)
Value low low limit
-10000.0...10000.0
Value deadband
100...100000
Update interval
0=No delay
1=10 ms
2=50 ms
3=100 ms
Table 104:
Output-specific settings for mA1 and mA2
Parameter
Values (Range)
Output mode
1=Not in use
6=0...20mA
Num of knee points
0...4
Input maximum
-10000.0...10000.0
Input knee point 4
-10000.0...10000.0
Input knee point 3
-10000.0...10000.0
Input knee point 2
-10000.0...10000.0
Input knee point 1
-10000.0...10000.0
Input minimum
-10000.0...10000.0
Value maximum
-20.0...20.0
Value knee point 4
-20.0...20.0
Value knee point 3
-20.0...20.0
Value knee point 2
-20.0...20.0
Value knee point 1
-20.0...20.0
Value minimum
-20.0...20.0
176
Unit
Step
Unit
Step
mA
mA
mA
mA
mA
mA
Default
Description
-10000
Output value low
alarm limit for
supervision
1000
Deadband
configuration value
for integral
calculation.
(percentage of
difference between
min and max as
0,001 % s)
0
Value update
interval
Default
Description
1=Not in use
Analog output mode
0
Number of knee
points in scaling
10000.0
Maximum analog
input value for mA
scaling
0.0
Input knee point
value 4 for scaling
0.0
Input knee point
value 3 for scaling
0.0
Input knee point
value 2 for scaling
0.0
Input knee point
value 1 for scaling
-10000.0
Minimum analog
input value for mA
scaling
20
Maximum analog
output value for mA
output
0
Knee point value 4
for output scaling
0
Knee point value 3
for output scaling
0
Knee point value 2
for output scaling
0
Knee point value 1
for output scaling
-20
Minimum analog
output value for mA
output
Technical Manual