Section 3
Basic functions
3.19.1.2
3.19.1.3
3.19.2
3.19.2.1
3.19.2.2
200

Functionality

The good signal quality function QTY_GOOD evaluates the quality bits of the input
signal and passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (except preprocessing
block). Due to application logic quality bit propagation, each (simple and even
combined) signal has quality which can be evaluated.
The OUT output indicates quality good of the input signal. Input signals that have no
quality bits set or only test bit is set, will indicate quality good status.

Signals

Table 150:
QTY_GOOD Input signals
Name
Type
IN
Any
Table 151:
QTY_GOOD Output signals
Name
Type
OUT
BOOLEAN

Bad signal quality QTY_BAD

Function block

GUID-E2612D94-CCE5-4BC3-BDC8-DDC94A96E0BD V1 EN
Figure 84:
Function block
Functionality
The bad signal quality function QTY_BAD evaluates the quality bits of the input
signal and passes it as a Boolean signal for the application.
The IN input can be connected to any logic application signal (except preprocessing
block). Due to application logic quality bit propagation, each (simple and even
combined) signal has quality which can be evaluated.
The OUT output indicates quality bad of the input signal. Input signals that have any
other than test bit set, will indicate quality bad status.
Default
Description
0
Input signal
Description
Output signal