Section 4
Protection functions
616
Vector group of the
Winding 1 type
transformer
Yzn7
Y
Yz11
Y
YNz11
YN
YNzn11
YN
Yzn11
Y
Zy1
Z
Zyn1
Z
ZNyn1
ZN
ZNy1
ZN
Zy5
Z
Zyn5
Z
ZNyn5
ZN
ZNy5
ZN
Zy7
Z
Zyn7
Z
ZNyn7
ZN
ZNy7
ZN
Yy0
Y
Commissioning
The correct settings, which are CT connection type, Winding 1 type, Winding 2 type
and Clock number, for the connection group compensation can be verified by
monitoring the angle values I_ANGL_A1_B1, I_ANGL_B1_C1,
I_ANGL_C1_A1, I_ANGL_A2_B2, I_ANGL_B2_C2, I_ANGL_C2_A2,
I_ANGL_A1_A2, I_ANGL_B1_B2 and I_ANGL_C1_C2 while injecting the
current into the transformer. These angle values are calculated from the compensated
currents. See signal description from Monitored data table.
When a station service transformer is available, it can be used to provide current to the
high voltage side windings while the low voltage side windings are short-circuited.
This way the current can flow in both the high voltage and low voltage windings. The
commissioning signals can be provided by other means as well. The minimum current
to allow for phase current and angle monitoring is 0.015 I
Winding 2 type
Clock number
zn
Clk Num 7
z
Clk Num 11
z
Clk Num 11
zn
Clk Num 11
zn
Clk Num 11
y
Clk Num 1
yn
Clk Num 1
yn
Clk Num 1
y
Clk Num 1
y
Clk Num 5
yn
Clk Num 5
yn
Clk Num 5
y
Clk Num 5
y
Clk Num 7
yn
Clk Num 7
yn
Clk Num 7
y
Clk Num 7
y
Clk Num 0
1MRS759142 C
Zro A Elimination
Not needed
Not needed
Not needed
LV side
Not needed
Not needed
Not needed
HV side
Not needed
Not needed
Not needed
HV side
Not needed
Not needed
Not needed
HV side
Not needed
Not needed
.
r
REX640
Technical Manual