1MRS759142 C
4.5.10.9
4.5.10.10
4.6
4.6.1
4.6.1.1
REX640
Technical Manual
Monitored data
Table 801:
PHVPTOV Monitored data
Name
Type
START_DUR
FLOAT32
U_MEAN_A
FLOAT32
U_MEAN_B
FLOAT32
U_MEAN_C
FLOAT32
U_MEAN_AB
FLOAT32
U_MEAN_BC
FLOAT32
U_MEAN_CA
FLOAT32
PHVPTOV
Enum
Technical data
Table 802:
PHVPTOV Technical data
Characteristic
Operation accuracy
Reset ratio
Operate time accuracy in definite time mode
Frequency protection
Frequency protection FRPFRQ
Identification
Function description
Frequency protection
Protection functions
Values (Range)
Unit
0.00...100.00
%
0.00...5.00
xUn
0.00...5.00
xUn
0.00...5.00
xUn
0.00...5.00
xUn
0.00...5.00
xUn
0.00...5.00
xUn
1=on
2=blocked
3=test
4=test/blocked
5=off
Value
Depending on the frequency of the measured
voltage: f
n
±1.5% of the set value or ±0.002 × U
Depends on the set
±1.0% of the set value or ±20 ms
IEC 61850
IEC 60617
identification
identification
FRPFRQ
f>/f<,df/dt
Section 4
Description
Ratio of start time /
operate time
Mean value of phase to
earth voltage A
Mean value of phase to
earth voltage B
Mean value of phase to
earth voltage C
Mean value of Phase to
phase voltage AB
Mean value of Phase to
phase voltage BC
Mean value of Phase to
phase voltage CA
Status
n
Relative hysteresis
ANSI/IEEE C37.2
device number
81
837