1MRS759142 C
4.1.5.10
4.1.6
4.1.6.1
4.1.6.2
4.1.6.3
4.1.6.4
REX640
Technical Manual
Technical data
Table 416:
T2PTTR Technical data
Characteristic
Operation accuracy
1)
Operate time accuracy
1) Overload current > 1.2 x Operate level temperature
Motor load jam protection JAMPTOC
Identification
Function description
Motor load jam protection
Function block
GUID-5EEB847C-34E3-4126-9985-97B54214A7D6 V1 EN
Figure 206:
Function block
Functionality
The motor load jam protection function JAMPTOC is used for protecting the motor in
stall or mechanical jam situations during the running state.
When the motor is started, a separate function is used for the startup protection, and
JAMPTOC is normally blocked during the startup period. When the motor has passed
the starting phase, JAMPTOC monitors the magnitude of phase currents. The function
starts when the measured current exceeds the breakdown torque level, that is, above
the set limit. The operation characteristic is definite time.
The function contains a blocking functionality. It is possible to block the function
outputs.
Analog channel configuration
JAMPTOC has one analog group input which must be properly configured.
Protection functions
Value
Depending on the frequency of the measured
current: f
±2 Hz
n
Current measurement: ±1.5% of the set value or
±0.002 x I
(at currents in the range of 0.01...4.00
n
x I
)
n
±2.0% of the theoretical value or ±0.50 s
IEC 61850
IEC 60617
identification
identification
JAMPTOC
Ist>
Section 4
ANSI/IEEE C37.2
device number
50TDJAM
375