Functionality
The integer value event creation function MVI4GAPC is used for creation of the
events from the integer values. The integer input value is received via IN1...4
input. The integer output value is available on OUT1...4 output.
The integer input range is from -2147483648 to 2147483647.
Signals
Table 218:
MVI4GAPC Input signals
Name
Type
IN1
INT32
IN2
INT32
IN3
INT32
IN4
INT32
Table 219:
MVI4GAPC Output signals
Name
Type
OUT1
INT32
OUT2
INT32
OUT3
INT32
OUT4
INT32
Analog value event creation with scaling SCA4GAPC
Identification
Function description
Analog value event creation with scaling
Function block
GUID-0442083C-FE4E-496A-9135-6E4C7D8706FB V1 EN
Figure 119:
Function block symbol
Default
Description
0
Integer input value 1
0
Integer input value 2
0
Integer input value 3
0
Integer input value 4
Description
Integer output value 1
Integer output value 2
Integer output value 3
Integer output value 4
IEC 61850
IEC 60617
identification
identification
SCA4GAPC
SCA4
Section 3
Basic functions
ANSI/IEEE C37.2
device number
SCA4