Section 4
Protection functions
4.3.5.11
Table 617:
HREFPDIF Group settings (Basic)
Parameter
Operate value
Minimum operate time
Table 618:
HREFPDIF Non group settings (Basic)
Parameter
Operation
Table 619:
HREFPDIF Non group settings (Advanced)
Parameter
Reset delay time
4.3.5.12
686
Table 616:
HREFPDIF Output signals
Name
OPERATE
START

Settings

Values (Range)
Unit
1.0...50.0
%In
40...300000
ms
Values (Range)
Unit
1=on
5=off
Values (Range)
Unit
0...60000
ms

Monitored data

Table 620:
HREFPDIF Monitored data
Name
START_DUR
HREFPDIF
Type
Description
BOOLEAN
Operate
BOOLEAN
Start
Step
Default
0.1
1.0
1
40
Step
Default
1=on
Step
Default
1
20
Type
Values (Range)
FLOAT32
0.00...100.00
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
1MRS759142 C
Description
Low operate value, percentage of the
nominal current
Minimum operate time
Description
Operation Off / On
Description
Reset delay time
Unit
Description
%
Ratio of start time /
operate time
Status
Technical Manual
REX640