ABB RELION REX640 Technical Manual page 574

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
568
I
I
L
2
L
1
I
L mLV
=
2
3
GUID-607DB035-0F0D-4EAA-858E-6FA06E0A1A8E V1 EN
I
I
L
3
L
2
I
L mLV
3
=
3
GUID-926E4327-8A74-44AB-BC63-819BFD1C3649 V1 EN
The "Y" side currents stay untouched, while the "d" side currents are compensated to
match the currents actually flowing in the windings.
In this example there is no neutral current on either side of the transformer (assuming
there are no earthing transformers installed). In the previous example, the matching is
done differently to have the winding 1 neutral current compensated at the same time.
Table 572:
LNPLDF vector group matching
Vector group of the
Winding 1 type
transformer
Yy0
YNy0
YNyn0
Yyn0
Yy2
YNy2
YNyn2
Yyn2
Yy4
YNy4
YNyn4
Yyn4
Yy6
YNy6
YNyn6
Yyn6
Yy8
YNy8
YNyn8
Yyn8
Yy10
YNy10
YNyn10
Yyn10
Yd1
Table continues on next page
Winding 2 type
Y
y
YN
y
YN
yn
Y
yn
Y
y
YN
y
YN
yn
Y
yn
Y
y
YN
y
YN
yn
Y
yn
Y
y
YN
y
YN
yn
Y
yn
Y
y
YN
y
YN
yn
Y
yn
Y
y
YN
y
YN
yn
Y
yn
Y
d
1MRS759142 C
(Equation 96)
(Equation 97)
Phase shift
Zero sequence
current elimination
0
Not needed
0
HV side
0
HV & LV side
0
LV side
2
Not needed
2
(Automatic)
2
(Automatic)
2
(Automatic)
4
Not needed
4
(Automatic)
4
(Automatic)
4
(Automatic)
6
Not needed
6
HV side
6
HV & LV side
6
LV side
8
Not needed
8
(Automatic)
8
(Automatic)
8
(Automatic)
10
Not needed
10
(Automatic)
10
(Automatic)
10
(Automatic)
1
Not needed
Technical Manual
REX640