Section 4
Protection functions
Parameter
Operating curve type
Operate delay time
Characteristic angle
Max forward angle
Max reverse angle
Min forward angle
Min reverse angle
Voltage start value
Table 491:
DEFLPDEF Group settings (Advanced)
Parameter
Type of reset curve
Operation mode
Enable voltage limit
Table 492:
DEFLPDEF Non group settings (Basic)
Parameter
Operation
Curve parameter A
Curve parameter B
Table continues on next page
440
Values (Range)
Unit
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
50...300000
ms
-179...180
deg
0...180
deg
0...180
deg
0...180
deg
0...180
deg
0.010...1.000
xUn
Values (Range)
Unit
1=Immediate
2=Def time reset
3=Inverse reset
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
0=False
1=True
Values (Range)
Unit
1=on
5=off
0.0086...120.0000
0.0000...0.7120
Step
Default
15=IEC Def. Time
10
50
1
-90
1
80
1
80
1
80
1
80
0.001
0.010
Step
Default
1=Immediate
1=Phase angle
1=True
Step
Default
1=on
1
28.2000
1
0.1217
1MRS759142 C
Description
Selection of time delay curve type
Operate delay time
Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Voltage start value
Description
Selection of reset curve type
Operation criteria
Enable voltage limit
Description
Operation Off / On
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Technical Manual
REX640