Signals; Goose Communication Quality Qty_Goose_Comm; Function Block; Functionality - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
3.19.2.3
3.19.3
3.19.3.1
3.19.3.2
3.19.3.3
REX640
Technical Manual

Signals

Table 152:
QTY_BAD Input signals
Name
Type
IN
Any
Table 153:
QTY_BAD Output signals
Name
Type
OUT
BOOLEAN

GOOSE communication quality QTY_GOOSE_COMM

Function block

GUID-338D1150-4CF5-4765-A48F-F661E093AB96 V1 EN
Figure 85:
Function block

Functionality

The GOOSE communication quality function QTY_GOOSE_COMM evaluates the
peer device communication status from the quality bits of the input signal and passes
it as a Boolean signal to the application.
The IN input can be connected to any GOOSE application logic output signal, for
example, GOOSERCV_BIN.
The OUT output indicates the communication status of the GOOSE function block.
When the output is in the true (1) state, the GOOSE communication is active. The
value false (0) indicates communication timeout.
Signals
Table 154:
QTY_GOOSE_COMM Input signals
Name
Type
IN
Any
Table 155:
QTY_GOOSE_COMM Output signals
Name
COMMVALID
Default
0
Description
Output signal
Default
0
Type
BOOLEAN
Section 3
Basic functions
Description
Input signal
Description
Input signal
Description
Output signal
201