1MRS759142 C
REX640
Technical Manual
First, voltage U
, ignoring the CT saturation during the fault, is calculated with the
max
equation
I
k
max
in
U
R
R
(
=
+
max
in
m
n
GUID-C3B7E72F-852E-4707-8E45-0C0BA3F89754 V1 EN
I
the maximum fault current inside the zone, in primary amps
kmaxin
n
the turns ration of the CT
R
the internal resistance of the CT in ohms
in
R
the resistance of the longest loop of the CT secondary circuit, in ohms
m
R
the resistance of the stabilized resistor, in ohms
s
Next, the peak voltage û, which includes the CT saturation, is estimated with the
formula (given by P.Mathews, 1955)
ß
2 2
U
U
U
(
=
kn
max
kn
GUID-30DA0307-3C85-44A2-A3C0-CA2C288B286B V1 EN
U
the knee point voltage of the CT
kn
The VDR is recommended when the peak voltage û ≥ 2kV, which is the insulation
level for which the protection relay is tested.
If R
was smaller, the VDR could be avoided. However, the value of R
s
protection relay operation current and stabilizing voltage. Thus, either a higher setting
must be used in the protection relay or the stabilizing voltage must be lowered.
I
k
max
in
R
R
)
+
s
s
n
)
Section 4
Protection functions
(Equation 134)
(Equation 135)
depends on the
s
681