1MRS759142 C
5.1.6
REX640
Technical Manual
Timer
Once activated, Timer runs until the set Operate delay time value is exceeded. The
time characteristics is according to DT. When the operation timer has reached the
Operate delay time value, the Timer module output is activated. If the timer has
elapsed and the inrush situation still exists, the Timer module output remains active
until the I_2H/I_1H ratio drops below the set Start value, that is, until the inrush
situation is over. If the drop-off situation occurs within the operate time up counting,
the reset timer is activated. If the drop-off time exceeds Reset delay time, the operate
timer is reset.
The BLOCK input can be controlled with a binary input, a horizontal communication
input or an internal signal of the relay program. The activation of the BLOCK input
prevents the BLK2H output from being activated.
Phase selection logic
This module determines the number of phases used for activating the BLK2H output.
If Num of start phases = "1 out of 3", an inrush on any of the phases activates output
BLK2H. If the set value equals "2 out of 3", an inrush or at least two phases are required
to activate output BLK2H.

Application

Transformer protections require high stability to avoid tripping during magnetizing
inrush conditions. A typical example of an inrush detector application is doubling the
start value of an overcurrent protection during inrush detection.
The inrush detection function can be used to selectively block overcurrent and earth-
fault function stages when the ratio of the second harmonic component to the
fundamental component exceeds the set value.
Other applications of this function include the detection of inrush in lines connected
to a transformer.
Protection related functions
Section 5
1063