Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
9.1.6
REX640
Technical Manual

Signals

Table 1300:
CBXCBR Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ENA_OPEN
BOOLEAN
ENA_CLOSE
BOOLEAN
BLK_OPEN
BOOLEAN
BLK_CLOSE
BOOLEAN
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
TRIP
BOOLEAN
SYNC_OK
BOOLEAN
SYNC_ITL_BYP
BOOLEAN
Table 1301:
DCXSWI Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ENA_OPEN
BOOLEAN
ENA_CLOSE
BOOLEAN
BLK_OPEN
BOOLEAN
BLK_CLOSE
BOOLEAN
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
ITL_BYPASS
BOOLEAN
Table 1302:
ESXSWI Input signals
Name
Type
POSOPEN
BOOLEAN
POSCLOSE
BOOLEAN
ENA_OPEN
BOOLEAN
ENA_CLOSE
BOOLEAN
BLK_OPEN
BOOLEAN
BLK_CLOSE
BOOLEAN
AU_OPEN
BOOLEAN
AU_CLOSE
BOOLEAN
ITL_BYPASS
BOOLEAN
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
1=True
Enables opening
1=True
Enables closing
0=False
Blocks opening
0=False
Blocks closing
0=False
Auxiliary open
0=False
Auxiliary close
0=False
Trip signal
1=True
Synchronism-check OK
0=False
Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
1=True
Enables opening
1=True
Enables closing
0=False
Blocks opening
0=False
Blocks closing
0=False
Auxiliary open
0=False
Auxiliary close
0=False
Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
Default
Description
0=False
Signal for open position of apparatus from I/O
0=False
Signal for close position of apparatus from I/O
1=True
Enables opening
1=True
Enables closing
0=False
Blocks opening
0=False
Blocks closing
0=False
Auxiliary open
0=False
Auxiliary close
0=False
Discards ENA_OPEN and ENA_CLOSE
interlocking when TRUE
Section 9
Control functions
1359