Section 9
Control functions
9.5.7
1396
GUID-9E70FE04-85E5-4A6E-8B98-FFBB4AE1433E V1 EN
Figure 748:
Connection of voltages for the protection relay and signals used in
synchrocheck

Signals

Table 1346:
SECRSYN Input signals
Name
Type
U3P1
SIGNAL
U3P2
SIGNAL
BLOCK
BOOLEAN
CL_COMMAND
BOOLEAN
BYPASS
BOOLEAN
Table 1347:
SECRSYN Output signals
Name
Type
SYNC_INPRO
BOOLEAN
SYNC_OK
BOOLEAN
CL_FAIL_AL
BOOLEAN
CMD_FAIL_AL
BOOLEAN
LLDB
BOOLEAN
LLLB
BOOLEAN
DLLB
BOOLEAN
DLDB
BOOLEAN
Default
Description
-
Three-phase voltages 1
-
Three-phase voltages 2
0=False
Blocking signal of the synchro check and voltage
check function
0=False
External closing request
0=False
Request to bypass synchronism check and voltage
check
Description
Synchronizing in progress
Systems in synchronism
CB closing failed
CB closing request failed
Live Line, Dead Bus
Live Line, Live Bus
Dead Line, Live Bus
Dead Line, Dead Bus