1MRS759142 C
REX640
Technical Manual
Operation mode
Freq< + df/dt
Table continues on next page
Protection functions
Description
A consecutive operation is enabled between the
protection methods. When the measured
frequency is below the set value of the
Freq< setting, the frequency gradient protection is
enabled. After the frequency has dropped below
the set value, the frequency gradient is compared
Start value df/dt setting.
to the set value of the
When the frequency gradient exceeds the set
value, the module activates the START and
STR_FRG outputs. The time characteristic is
according to DT. When the operation timer has
reached the value set by the
setting, the OPERATE and OPR_FRG outputs are
activated. If the frequency gradient restores before
the module operates, the reset timer is activated. If
the timer reaches the value set by the
Tm df/dt setting, the operate timer resets and the
START and STR_FRG outputs are deactivated.
The OPR_UFRQ output is not active when this
operation mode is used.
Section 4
Start value
Operate Tm df/dt
Reset delay
841