Section 3
Basic functions
3.17.1.5
Table 122:
ILTCTR Non group settings (Basic)
Parameter
Current input type
Primary current
Secondary current
Rated secondary Val
Amplitude Corr A
Amplitude Corr B
Amplitude Corr C
Angle Corr A
Angle Corr B
Angle Corr C
Table 123:
ILTCTR Non group settings (Advanced)
Parameter
Reverse polarity
Frequency adaptivity
3.17.1.6
184
Name
IL3_DR
NPS_DR
PPS_DR

Settings

Values (Range)
Unit
2=Current trafo
4=Current sensor
1.0...15000.0
A
2=1A
3=5A
1.000...150.000
mV/Hz
0.9000...1.1000
0.9000...1.1000
0.9000...1.1000
-20.0000...20.0000
deg
-20.0000...20.0000
deg
-20.0000...20.0000
deg
Values (Range)
Unit
0=False
1=True
0=Disable
1=Enable
3=Backup
frequency source

Monitored data

Monitored data is available in three locations.
Monitoring/I/O status/Analog inputs
Monitoring/IED status/SMV traffic
Monitoring/IED status/SMV accuracy
Type
Description
SIGNAL
Phase current IL3 for disturbance recorder
SIGNAL
Negative sequence current for disturbance
recorder
SIGNAL
Positive sequence current for disturbance recorder
Step
Default
2=Current trafo
0.1
100.0
2=1A
0.001
3.000
0.0001
1.0000
0.0001
1.0000
0.0001
1.0000
0.0001
0.0000
0.0001
0.0000
0.0001
0.0000
Step
Default
0=False
0=Disable
1MRS759142 C
Description
Type of the current input
Rated primary current
Rated secondary current
Rated Secondary Value (RSV) ratio
Phase A amplitude correction factor
Phase B amplitude correction factor
Phase C amplitude correction factor
Phase A angle correction factor
Phase B angle correction factor
Phase C angle correction factor
Description
Reverse the polarity of the phase CTs
Frequency adaptivity selection
Technical Manual
REX640