Section 3
Basic functions
Table 58:
Station authority level "L,S,R" using CONTROL function block
L/R Control
Control FB input CTRL.LLN0.LocSta
CTRL_OFF
FALSE
CTRL_LOC
FALSE
CTRL_STA
TRUE
TRUE
4)
CTRL_REM
CTRL_REM
FALSE
CTRL_ALL
FALSE
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
3.8.7
128
L/R Control status
CTRL.LLN0.MltLev
1)
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE

Station authority level "L,S,S+R,L+S,L+S+R"

Station authority level "L,S,S+R,L+S,L+S+R" adds station control access together
with several different multilevel access scenarios. Control access can also be
simultaneously permitted from local, station or remote location. Simultaneous local,
station or remote control operation is not allowed as one client and location at time can
access controllable objects and they remain reserved until the previously started
control operation is first completed by the client.
LOCAL
STATION
IEC 61850
IEC 61850
remote
remote
IEC 61850
IEC 61850
station
station
IED
IED
GUID-5A432A20-50D4-4DD3-8EA4-2DAE5B18BED1 V1 EN
Figure 41:
Station authority is "L,S,S+R,L+S,L+S+R"
When station authority level "L,S,S+R,L+S,L+S+R" is used, control access can be
selected using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input CTRL_STA are applicable
for this station authority level.
"Station" and "Local + Station" control access can be reserved by using R/L button or
CONTROL function block in combination with IEC 61850 data object
CTRL.LLN0.LocSta.
L/R state
CTRL.LLN0.LocKeyHMI
0
1
3
3
2
0
S+R
L+S
IEC 61850
remote
IEC 61850
IEC 61850
station
station
IED
1MRS759142 C
Control access
Local user
IEC 61850
2)
client
x
x
L+S+R
IEC 61850
IEC 61850
remote
remote
IEC 61850
station
IED
IED
Technical Manual
IEC 61850
3)
client
x
x
OFF
IEC 61850
remote
IEC 61850
station
IED
REX640