Functionality; Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 3
Basic functions
3.20.10.3
3.20.10.4
234

Functionality

The analog value event creation with scaling function SCA4GAPC is used for scaling
the analog value. It allows creating events from analog values.
The analog value received via the AIn_VALUE input is scaled with the Scale ratio n
setting. The scaled value is available on the AOn_VALUE output.
Analog input range is from -10000.0 to 10000.0.
Analog output range is from -2000000.0 to 2000000.0.
If the value of the AIn_VALUE input exceeds the analog input range,
AOn_VALUE is set to 0.0.
If the result of AIn_VALUE multiplied by the Scale ratio n setting
exceeds the analog output range, AOn_VALUE shows the minimum or
maximum value, according to analog value range.

Signals

Table 220:
SCA4GAPC Input signals
Name
Type
AI1_VALUE
FLOAT32
AI2_VALUE
FLOAT32
AI3_VALUE
FLOAT32
AI4_VALUE
FLOAT32
Table 221:
SCA4GAPC Output signals
Name
Type
AO1_VALUE
FLOAT32
AO2_VALUE
FLOAT32
AO3_VALUE
FLOAT32
AO4_VALUE
FLOAT32
Default
Description
0.0
Analog input value of channel 1
0.0
Analog input value of channel 2
0.0
Analog input value of channel 3
0.0
Analog input value of channel 4
Description
Analog value 1 after scaling
Analog value 2 after scaling
Analog value 3 after scaling
Analog value 4 after scaling
1MRS759142 C
REX640
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents