Siemens SIMOTION D4x5-2 Commissioning And Hardware Installation Manual page 401

Hide thumbs Also See for SIMOTION D4x5-2:
Table of Contents

Advertisement

Table 9-9
Status
Backup in progress
Backup complete
DIAG button (alternative)
To back up data via the DIAG button, proceed as follows:
1. Switch the D4x5-2 off.
2. Press the DIAG button and hold it down. Switch the D4x5-2 on.
3. Wait for the device to ramp up.
The diagnostic data and non-volatile SIMOTION data are backed up to the CF card during
power-up, provided that this is still possible and is not prevented by hardware defects, for
example.
4. Once the backup is complete, you can release the button and switch off the D4x5‑2.
5. Remove the CF card.
Table 9-10
Status
Backup in progress
Backup complete
INI file in the main directory of the CF card
1. Use a text editor (such as Notepad) to create a file called
2. Add the following text: DIAG_FILES=1
You must use a text editor and may not use any formatting in the text.
3. Copy the simotion.ini file to the main directory of the CF card.
4. Insert the CF card into the module, which is switched off.
5. Switch the D4x5‑2 on and allow the SIMOTION device to power up.
The diagnostic data and the non-volatile SIMOTION data will be backed up to the data
carrier during power-up, provided that this is still possible and is not prevented by HW
defects, for example.
6. Once the backup is complete, switch off the SIMOTION device.
7. Remove the CF card.
Note
To suppress startup in diagnostics mode again, you must delete the
the CF card.
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
LED displays during backup
LED displays on the D4x5‑2
STOP LED and SU/PF LED flicker yellow
RUN LED flickers green
LED displays during backup
LED displays on the D4x5‑2
STOP LED and SU/PF LED flicker yellow
RUN LED flickers green
9.2 Diagnostic data and non-volatile SIMOTION data
simotion.ini
Diagnostics
simotion.ini file from
401

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion cx32-2Simotion cbe30-2Simotion tb30

Table of Contents