Creating A Dmc20/Dme20 Drive-Cliq Hub - Siemens SIMOTION D4x5-2 Commissioning And Hardware Installation Manual

Hide thumbs Also See for SIMOTION D4x5-2:
Table of Contents

Advertisement

Additional references
Additional information on the DMC20/DME20 DRIVE‑CLiQ is contained in the
SIMOTION D4x5‑2 Manual
SINAMICS S120 Control Units and Additional System Components Manual
7.14.2

Creating a DMC20/DME20 DRIVE-CLiQ hub

Introduction
A DMC20/DME20 can be inserted directly in the project navigator. The hub is not wired when
you insert the DMC20/DME20 and is displayed in the topology tree in the component storage.
The hub has to be wired manually.
Procedure
1. Right-click "Topology" in the project navigator.
2. Select the "Insert new object" > "DRIVE‑CLiQ hub" command from the context menu and
confirm with "OK".
3. Double-click "Topology" to display the topology tree.
In the topology tree, the hub is stored in the component archive.
4. Drag-and-drop the hub to the required DRIVE‑CLiQ interface.
The components connected to the hub are displayed in the topology tree.
Result
The added hub is displayed for the "Topology" entry in the project navigator. All components
connected to a hub are also displayed during an automatic configuration.
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
Commissioning (software)
7.14 DMC20/DME20 DRIVE-CLiQ hub
297