9.1.11 How Do I Calibrate a T/H Sensor?

Context
Calibrate a sensor if the displayed temperature or humidity values on the sensor
deviate from the actual values. For example, if the return air temperature
measured by other temperature detection device at the return air detection point
is 20°C while the sensor measured 22°C, the sensor has an error of 2°C, and the
calibration value can be set to –2°C.
Procedure
Step 1 Choose Maint > Sensor Calibration on the home screen.
Step 2 Fill the calibration value based on the measured error.
----End

9.1.12 How Do I Change the Password?

Prerequisites
Procedure
Step 1 On the home screen, choose Settings > User Settings. The User Settings screen is
displayed.
Issue 01 (2021-01-30)
NO TICE
If you need to change a password, log in as user admin or operator.
You can only modify the password of the current user.