FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 3-13 Pipe anti-freezing solution
(1) Water seal
(3) Water refill pipe
(5) Soil
Figure 3-14 Requirement for wrapping the electric heating belt
● The temperature control switch is integrated with the electric heating belt. The
electric heating belt needs to be coiled evenly on the drainpipe and water refill
pipe during onsite construction. The temperature control switch is installed on
the post inside the maintenance door.
● Wrap the electric heating belt and then wrap the thermal insulation foam.
Ensure that the thermal insulation foam covers the temperature control switch
and temperature sensor probe. The thermal insulation foam must withstand a
temperature above 200°C.
Issue 01 (2021-01-30)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
3 System Installation (Building Scenario)
(2) Electric heating belt
(4) Drainpipe (connected to the utility
drainpipes)