Optional) Installing Electric Heater Components And Cables - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Locati
on
● The default T/H sensor address is 1.
● Keep the last RS485_R DIP switch at OFF.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen, and set the sensors in the aisles
corresponding to the addresses to Enable. Otherwise, the sensors will not work.
----End
4.6 (Optional) Installing Electric Heater Components
and Cables
Electric heater components include the electric heating belt, temperature sensor
probe, and electric heater controller.
Procedure
Step 1 Remove the exhaust side panel.
Step 2 Install the electric heater controller.
Issue 01 (2021-01-30)
Display Name
Hot aisle 3
temp/humid
Hot aisle 4
temp/humid
Hot aisle 5
temp/humid
Hot aisle 6
temp/humid
NO TICE
Copyright © Huawei Technologies Co., Ltd.
4 System Installation (FDC Scenario)
Add
DIP Switch No.
ress
1
2
23
ON
ON
24
OFF
OFF
25
ON
OFF
26
OFF
ON
3
4
5
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
6
OFF
OFF
OFF
OFF
87