FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 4-7 Securing the unit
Step 8 Close the maintenance door after the unit is secured.
----End
4.3.3 Checking the Refrigerant
Procedure
Step 1 Remove the adjustable side panels for the compressor.
Step 2 Check whether any of the needle valve bonnets shown in
1.
2.
Issue 01 (2021-01-30)
NO TE
This section uses two-layer stacking as an example.
If any bonnet is missing, contact Huawei technical support.
If no bonnet is missing, remove the valve bonnets, and press the valve plugs
using the valve bonnets in turn. If gas flows out, the system is normal. If no
gas flows out, contact Huawei technical support.
Copyright © Huawei Technologies Co., Ltd.
4 System Installation (FDC Scenario)
Figure 4-8
is missing.
70